Facade Systems
Concealed Fastener Rainscreen System
System Depth = 1 1/2” + Zee Girt
Joint Width = 3/8”
 
System Components:
1.    Trespa®  Meteon® Panel
2.    Universe Hanger Rail Extrusion – Black Color (Shop Attached)
3.    Universe Intermediate Rail Extrusion – Black Color
4.    Extrusion Fastener
5.    Fixed Bracket (Shop Attached)
6.    (2) 1/4” Thermal Isolators
7.    Zee Girt
8.    Mineral Wool Insulation
9.    Air & Moisture Barrier
10.    Sheathing
11.    16 Gauge Min. Steel Stud
 
Notes:
•    Horizontally attached across framing.
•    Thermal Isolators (6) are required at each Fixed Bracket Clip (5).
•    Insulation (8) must be mineral wool. Foam plastic insulation triggers NFPA-285 fire code which requires a tested assembly.  The only other option is to acquire an AHJ approval. Receiving an AHJ approval is not guaranteed. It must be the same depth as the zee girt (7).
•    Air & Moisture barrier (9) must be VaproShield® WallShield®, WrapShield®, RevealShield™, Cosella-Dorken Delta® Fassade-S, Delta® Foxx, Delta® Foxx-S, Tyvek® CommercialWrap®, Dow Corning DefendAir 200 or Momentive™ SEC2500-SilShield AWB if mineral wool (8) is less than 2” thick; if mineral wool is thicker than 2” then other barriers may be used.
•    Extrusions have splices for support between studs.
•    Available with 10mm and 13mm Trespa Meteon (1) panel thickness only.
•    The zee girt (7) is not painted.
 